PowerFlex 700L Technical Data
Publication 20L-TD001A 29
Control Connections
Frame 2
Frame 2 Control Terminal Locations
Frame 2 Control Terminal Specifications
Item Name Description
Wire Size Range
(1)
(1)
Maximum/minimum sizes that the terminals will accept - these are not recommendations.
Recommended Tightening
Torque (+
10%)
Wire Strip
LengthMaximum Minimum
➊
PowerFlex 700 Vector Control or
PowerFlex 700S Phase II Control
Cassette Terminal Blocks
See PowerFlex 700 Series B Tech Data (publication 20B-TD001) or
PowerFlex 700S Tech Data (publication 20D-TD002) respectively for details.
➋
Active Converter Cassette Terminal
Blocks — P1 & P2
Active Converter AC power and control wiring 3.3 mm
2
(#12 AWG)
0.3 mm
2
(#22 AWG)
0.8 N•m (7 lb•in) 8 mm
(0.31 in.)
➌
SHLD Terminal Terminating point for control wiring shields on the
drive
2.1 mm
2
(#14 AWG)
0.3 mm
2
(#22 AWG)
1.4 N•m (12 lb•in) 10 mm
(0.39 in.)
➍
Terminal Block — TB1
1b 5: +12/+24V Cooling Loop
1b 6: Cooling Loop Return
Drive control wiring:
Output dry contact (12V dc/24V dc, 2 Amps
max.) indicating the drive is powered and has
completed precharge.
4.0 mm
2
(#10 AWG)
0.2 mm
2
(#24 AWG)
0.9 N•m (8 lb•in) 8 mm
(0.31 in.)
1b 7: +24V (digin) Drive-supplied +24V dc
1b 8: Gate Enable Enables the firing of the IGBTs. Factory-
installed jumper from terminal 1b 7 to terminal
1b 8 allows firing of the IGBTs.
➎
PS- Terminal
PS+ Terminal
300V dc Auxiliary Control voltage 4.0 mm
2
(#12 AWG)
0.5 mm
2
(#22 AWG)
0.6 N•m (5.3 lb•in) 10 mm
(0.39 in.)
P1
P2
1
15
7
1
SHLD
SHLD
➊
➋
➌
TB1
Customer Connection Side
➍
1b15
1b14
1b13
1b12
1b11
1b10
1b9
1b8
1b7
1b6
1b5
1b4
1b3
1b2
1b1
PS-
PE1PE2
PE1PE2
PS+
1a15
1a14
1a13
1a12
1a11
1a10
1a9
1a8
1a7
1a6
1a5
1a4
1a3
1a2
1a1
PS-
PS+
Kommentare zu diesen Handbüchern