PowerFlex 700L Technical Data
Publication 20L-TD001A 23
Maximum Motor Cable Lengths
In the following tables, a “●” in any of the latter columns will indicate that this drive rating can be used with an Allen-
Bradley Terminator (1204-TFA1/1204-TFB2) and/or Reflected Wave Reduction Device with Common Mode Choke
(1204-RWC-17) or without choke (1204-RWR2).
For the Terminator, the maximum cable length is 182.9 meters (600 feet) for 400/480/600V drives (not 690V). The PWM
frequency must be 2 kHz.
The 1321-RWR is a complete reflected wave reduction solution available for many of the PowerFlex drives. If available, a
1321-RWR catalog number will be indicated in the “Reactor/RWR” column. When not available, use the reactor and
resistor information provided to build a solution.
PowerFlex 700L with 700VC Control, 400V Shielded/Unshielded Cable - Meters (Feet)
PowerFlex 700L with 700VC Control, 480V Shielded/Unshielded Cable - Meters (Feet)
For Further Information on… See Publication…
1204-TFxx 1204-IN002
Drive No Solution Reactor Only Reactor + Damping Resistor Reactor Resistor
Available
Options
Frame
HP
(kW) kHz 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
2 268
(200)
2 24.4
(80)
91.4
(300)
152.4
(500)
213.4
(700)
30.5
(100)
76.2
(250)
228.6
(750)
365.8
(1200)
152.4
(500)
274.3
(900)
365.8
(1200)
365.8
(1200)
1321-3R400-B
(1)
(1)
Requires two parallel cables.
20 495
●
4 24.4
(80)
91.4
(300)
121.9
(400)
152.4
(500)
18.3
(60)
76.2
(250)
137.2
(450)
182.9
(600)
76.2
(250)
137.2
(450)
274.3
(900)
365.8
(1200)
1321-3R400-B
(1)
20 990
3A 500
(370)
2 24.4
(80)
91.4
(300)
152.4
(500)
213.4
(700)
30.5
(100)
76.2
(250)
228.6
(750)
365.8
(1200)
152.4
(500)
274.3
(900)
365.8
(1200)
365.8
(1200)
1321-3R750-B
(1)
20 735
●
4 24.4
(80)
91.4
(300)
121.9
(400)
152.4
(500)
18.3
(60)
76.2
(250)
137.2
(450)
182.9
(600)
76.2
(250)
137.2
(450)
274.3
(900)
365.8
(1200)
1321-3R750-B
(1)
20 1470
3B 960
(715)
2 24.4
(80)
76.2
(250)
129.5
(425)
160.0
(525)
91.4
(80)
76.2
(250)
152.4
(500)
228.6
(750)
152.4
(500)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R600-B
(2)
(2)
Requires four parallel cables.
20 525
4 18.3
(60)
76.2
(250)
121.9
(400)
152.4
(500)
18.3
(60)
76.2
(250)
121.9
(400)
152.4
(500)
76.2
(250)
137.2
(450)
274.3
(900)
365.8
(1200)
2 x
1321-3R600-B
(2)
20 1050
Drive No Solution Reactor Only Reactor + Damping Resistor Reactor Resistor
Available
Options
Frame
HP
(kW) kHz 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
2 300
(224)
2 12.2
(40)
30.5
(100)
91.4
(300)
121.9
(400)
12.2
(40)
36.6
(120)
99.1
(325)
137.2
(450)
61.0
(200)
137.2
(450)
274.3
(900)
365.8
(1200)
1321-3R400-B
(1)
(1)
Requires two parallel cables.
20 495
●
47.6
(25)
24.4
(80)
83.8
(275)
114.3
(375)
7.6
(25)
24.4
(80)
83.8
(275)
114.3
(375)
30.5
(100)
61.0
(200)
152.4
(500)
213.4
(700)
1321-3R400-B
(1)
20 990
3A 600
(445)
2 12.2
(40)
30.5
(100)
91.4
(300)
121.9
(400)
12.2
(40)
36.6
(120)
99.1
(325)
137.2
(450)
61.0
(200)
137.2
(450)
274.3
(900)
365.8
(1200)
1321-3R750-B
(1)
20 735
●
47.6
(25)
24.4
(80)
83.8
(275)
114.3
(375)
7.6
(25)
24.4
(80)
83.8
(275)
114.3
(375)
30.5
(100)
61.0
(200)
152.4
(500)
213.4
(700)
1321-3R750-B
(1)
20 1470
3B 1150
(860)
2 12.2
(40)
24.4
(80)
83.8
(275)
114.3
(375)
12.2
(40)
30.5
(100)
91.4
(300)
121.9
(400)
61.0
(200)
137.2
(450)
274.3
(900)
365.8
(1200)
2 x
1321-3R600-B
(2)
(2)
Requires four parallel cables.
20 525
47.6
(25)
24.4
(80)
83.8
(275)
114.3
(375)
7.6
(25)
24.4
(80)
83.8
(275)
114.3
(375)
30.5
(100)
61.0
(200)
152.4
(500)
213.4
(700)
2 x
1321-3R600-B
(2)
20 1050
Kommentare zu diesen Handbüchern