Dimplex Thermal Solutions 1800-YOU-KOOL
Low refrigerant
pressure fault -
(Automatically
reset when
satisfied with
pressure)
Low ambient air temperature.
Loss of fluid flow through
evaporator.
Loss of refrigerant.
Refrigerant solenoid not
functional.
Faulty pressure switch.
Compressor crankcase not warm
or faulty crankcase heater.
Ensure chiller is operating within its
designed ambient temperature specification.
Check fluid flow and ensure evaporator is
clean.
Have a refrigerant technician leak check unit
and charge with the appropriate refrigerant.
Check wiring to solenoid or replace valve.
Replace pressure switch.
Ensure main power disconnect has been on
for at least 8 hours prior to use. Replace
crankcase heater if faulty.
High refrigerant
pressure fault -
(Manually reset
inside of chiller)
(Example of a
high pressure
switch shown)
AIR COOLED CHILLERS:
Air filters dirty.
Condenser dirty.
Incoming air too hot.
Inoperative fans.
Back panel out of chiller.
Phase rotation incorrect.
Refrigerant system overcharged.
WATER COOLED CHILLERS:
Low water flow to condenser.
Condenser dirty.
Regulating valve operating
incorrectly.
Refrigerant system overcharged.
Clean filters (See maintenance section).
Clean condenser (See maintenance section).
Ensure the chiller is properly ventilated with
fresh air not exceeding 90°F, unless
designed for high-ambient temperature
operation.
Check for blown fan fuses.
Ensure all covers and panels are in chiller.
Correct phase rotation at incoming power.
Have a refrigeration technician ensure the
system is properly charged.
Check condenser water supply and pressure.
Clean condenser.
Have a refrigeration technician adjust the
valve to the proper pressure setting and
check operation.
Have a refrigeration technician ensure the
system is properly charged.
Compressor
overload -
(May be manually
or automatically
reset, depending
on compressor)
Compressor running too hot.
Temperature setpoint too high.
Refrigerant pressures too high or
low.
Faulty overload module.
Low voltage to chiller.
Defective compressor.
Allow compressor to cool, then restart unit.
Move temperature setpoint to +/- 10°F of
factory setting.
Have a refrigeration technician monitor
pressures and determine cause.
If compressor will run, check amp draw on
compressor leads to verify compressor is ok.
Correct incoming voltage.
Replace compressor.