Dimplex Compact Air Curtains
Models : CAB10ER, CAB10WR, CAB10AR
CAB15ER, CAB15WR & CAB15AR
IMPORTANT: THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE
IMPORTANT SAFETY ADVICE
DO NOT COVER OR OBSTRUCT the air inlet or outlet
grille.
ENSURE THE APPLIANCE IS EARTHED.
Do not use this heater in areas where excessive dust
exists.
This heater must not be located immediately above or
below a fi xed socket outlet or connection box.
Always disconnect supply before working on the
product.
This appliance should only be connected to the fi xed
wiring of the premises by means of conduit.
This product should only be mounted safely to solid
ceiling surfaces.
This product must not be subjected to water spray or
immersion.
Ensure the supply cables are of adequate current
carrying capacity and are protected by a suitable fuse.
If the appliance is mounted in a toilet or washroom, the
appliance should be mounted such that no part of it can
be touched by a person using a fi xed bath or shower.
If the appliance is mounted in a toilet or washroom
an isolating switch must be provided outside the
washroom adjacent to the entrance door.
This appliance is not intended for use by persons
(including children) with reduced physical, sensory
or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person
responsible for their safety.
WARNING: Isolate electrical supply to ALL modular
linked units when carrying out maintenance.
Model Heat Output
kW
Electrical Supply Electrical
Load
(per phase)
Weight
KG
Max
Installed
height
M
AMBIENT / COLD STORE
CAB10AR n/a 220-240V ~1PN 0.3 20.5 3.0
CAB15AR n/a 220-240V ~1PN 0.5 29.5 3.0
ELECTRICALLY HEATED
CAB10ER 4.5 / 9.0 380-415V ~3PN 14 26 3.0
CAB15ER 6.75 / 13.5 380-415V ~3PN 20 35 3.0
WATER HEATED (at 82/71 °C - LPHW)**
CAB10WR 9.0 220-240V ~1PN 0.3 23 3.0
CAB15WR 13.5 220-240V ~1PN 0.5 32.5 3.0
Models
This range of air curtains are specifi cally designed to be
recessed into ceiling spaces and above suspended ceilings.
Electrical
The installation of this appliance should be carried out by a
competent electrician and be in accordance with the current IEE
wiring regulations.
Fixing Positions
This appliance must be mounted to a suitable ceiling - see Fig.
1 for fi xing dimensions and Fig. 5, 6, or 7 for mounting positions
and ‘Mounting’ sections below for fi xing details. This appliance
should not be mounted less than 1.8m from the fl oor.
Mounting into a Standard Ceiling Void
1. Side Fixings - Using a suitable ceiling surface, mark off and
drill for M8 drops rods. Dimensions can be found on Fig.1. Cut
the M8 drop rods to the desired length, taking note of the fi nal
position of the appliance relative to the distance to the mounting
surface. Mount the drop rods to the ceiling surface. Remove the
ceiling tiles on the appliance. (see Fig. 2) Using suitable lifting
equipment raise up the appliance to the drop rods as shown in
Fig. 5. Connect the appliance to the drop rods using standard M8
lock nuts and washers.
2. Top Mounted Inserts - If a suitable (unistrut) structure is
available, mark off and drill for M8 threaded bolts. Insert the bolts
down through the structure. Dimensions can be found on Fig.
1. Using suitable lifting equipment raise up the appliance to the
bolts. Screw the bolts into the threaded inserts on the top of the
appliance, and tighten securely.
Electrical connection
All products are fi tted with a microprocessor control. Electrical
power and control connections are made as shown in Fig. 4. A
suitable local isolating switch must be provided in the electrical
supply circuit with at least 3mm clearance on each pole. In order
to access the electrical connections, remove the outlet grilles (‘x’
in Fig. 2) by undoing the four fasteners in each tile. For the Water
heated and Ambient models only, the pressure plate must also be
removed.
All Electric Models - Having removed a ‘knock out’ in the
top panel, feed an appropriate supply cable (see ‘a’ in Fig. 4A)
through a suitable cable gland (not supplied) fi tted in the top
panel and attach to the terminal block (see ‘b’ in Fig. 4A).
All Water heated and Ambient Models - Having
removed a ‘knock out’ in the top panel, feed an appropriate
supply cable (see ‘a’ in Fig.4B) through a suitable cable gland
(not supplied) fi tted in the top panel and attach to the PCB (see
‘b’ in Fig. 4B).