Max external temperature for operation
Index - String
MIN
value
MAX
value
Parameter function
070
This parameter lets you establish the room temperature threshold above which the heat
pump is disabled; once the threshold has been exceeded, the compressor and pump are
switched off.
High temperature return water limit
Index - String
MIN
value
MAX
value
Parameter function
40 80
This parameter indicates the temperature of the return water above which the pump is
switched off and a pre-alarm is generated. After the intervention of the pre-alarm, there
is a waiting time of 15 minutes before the pump starts up again. After the third interven-
tion, the machine goes into alarm/lockout. Active also with the pump switched off, and
the heat pump in standby. In the latter case, the alarm is generated.
Screensaver configuration
Index - String
MIN
value
MAX
value
Parameter function
0 2 This parameter indicates the configuration of the screensaver:
• value 0, screensaver disabled;
• value 1, screensaver with visualisation of the dashes;
• value 2, screensaver without visualisation of the dashes (to be used with the control
panels with software from version 1.3 onwards).
Modbus supervisor address
Index - String
MIN
value
MAX
value
Parameter function
1 999
This parameter indicates the modbus address that the supervisor (if implemented and
provided in the installation) must use to communicate with the moducontrol board.
Supervisor baud rate
Index - String
MIN
value
MAX
value
Parameter function
02
This parameter selects the baud rate to be used in communications with the supervisor
(8 bit data, N-parity, 2 stop bits):
• value 0 = 9600 bps;
• value 1 = 19200 bps;
• value 2 = 38400 bps;
Enable Supervisor write commands
Index - String
MIN
value
MAX
value
Parameter function
01
This parameter enables or disables write commands from the supervisor (read com-
mands are permanently enabled):
• value 0 = write commands disabled;
• value 1 = write commands enabled;